EN12193 Requirements
Class I | Class II | Class III | |||
---|---|---|---|---|---|
Horizontal illuminance Infield | Em lx | 750 | 500 | 300 | |
Emin/Emax | 0.7 | 0.7 | 0.5 | ||
Horizontal illuminance Outfield | Em lx | 500 | 300 | 200 | |
Emin/Emax | 0.5 | 0.5 | 0.3 |
Baseball or softball requires high levels of illumination to enable the action and ball flight to be followed. Most fast actions take place
in the infield, which will require a significantly higher illuminance and over all uniformity than the larger outfield. Floodlighting must
achieve good modelling of players and minimize shadowing, meanwhile control glare to players, officials and spectators.
Baseball is unique in having nine fixed lines of sight within which pole locations should be avoided if glare from floodlighting is to be
adequately controlled, because of the regulation infield layout of pitcher, hitter and three base-plate fielders. Poles are not permitted
within a 90° zone directly behind the home plate, to ensure good viewing conditions for outfielders. These pole placement regulations
generally dictate the use of either six or eight-pole floodlighting systems, with floodlights aimed to illuminate infield diamond, far
infield/near outfield and deep outfield. The provision of at least bi-directional lighting into each zone is necessary if adequate
modelling of players is to be achieved.
EN12193 Requirements
Class I | Class II | Class III | |||
---|---|---|---|---|---|
Horizontal illuminance Infield | Em lx | 750 | 500 | 300 | |
Emin/Emax | 0.7 | 0.7 | 0.5 | ||
Horizontal illuminance Outfield | Em lx | 500 | 300 | 200 | |
Emin/Emax | 0.5 | 0.5 | 0.3 |
Poles | 8 x 70ft |
Floodlight | 62 x Model A 2400W |
Floodlight Type | 24 x MBE2400-T10D-50K-3535A 18 x MBE2400-T20D-50K-3535A 20 x MBE2400-T40D-50K-3535A |
System Power | 148.8KW |
Eh Ave Infield | >150 fc |
Emax/Emin | <1.16 |
Eh Ave Outfield | >100 fc |
Emax/Emin | <1.45 |
GR Max | 45 |
ULR | 5.0% |
Poles | 8 x 70ft |
Floodlight | 42 x Model A 2400W |
Floodlight Type | 14 x MBE2400-T10D-50K-3535A 12 x MBE2400-T20D-50K-3535A 16 x MBE2400-T40D-50K-3535A |
System Power | 100.8KW |
Eh Ave Infield | >100 fc |
Emax/Emin | <1.22 |
Eh Ave Outfield | >75 fc |
Emax/Emin | <1.25 |
GR Max | 45 |
ULR | 5.0% |
Poles | 6 x 70ft |
Floodlight | 24 x Model A 1920W |
Floodlight Type | 20 x MBE1920-T20D-50K-3535A 4 x MBE1920-T40D-50K-3535A |
System Power | 46.08KW |
Eh Ave Infield | >50 fc |
Emax/Emin | <1.4 |
Eh Ave Outfield | >30 fc |
Emax/Emin | <1.87 |
GR Max | 46 |
ULR | 5.5% |
Poles | 6 x 70ft |
Floodlight | 2 x Model A 1440W + 14 x Model A 1920W |
Floodlight Type | 2 x MBE1440-T60D-50K-3535A 4 x MBE1920-T20D-50K-3535A 10 x MBE1920-T40D-50K-3535A |
System Power | 29.76KW |
Eh Ave Infield | >30 fc |
Emax/Emin | <1.48 |
Eh Ave Outfield | >20 fc |
Emax/Emin | <1.93 |
GR Max | 47 |
ULR | 3.5% |
Poles | 8 x 18m |
Floodlight | 2 x Model A 960W + 16 x Model A 1440W |
Floodlight Type | 2 x MBE960-T40D-50K-3535A 4 x MBE1440-T20D-50K-3535A 6 x MBE1440-T40D-50K-3535A 6 x MBE1440-T60D-50K-3535A |
System Power | 24.96KW |
Eh Ave Infield | >750 lux |
Emin/Emax | >0.72 |
Eh Ave Outfield | >500 lux |
Emin/Emax | >0.56 |
GR Max | 40 |
ULR | 3% |
Poles | 8 x 18m |
Floodlight | 8 x Model A 960W + 4 x Model A 1920W |
Floodlight Type | 6 x MBE960-T40D-50K-3535A 2 x MBE960-T60D-50K-3535A 4 x MBE1920-T60D-50K-3535A |
System Power | 15.36KW |
Eh Ave Infield | >500 lux |
Emin/Emax | >0.73 |
Eh Ave Outfield | >300 lux |
Emin/Emax | >0.52 |
GR Max | 34 |
ULR | 1.5% |
Poles | 6 x 18m |
Floodlight | 2 x Model A 1440W + 4 x Model A 1920W |
Floodlight Type | 2 x MBE1440-T4VVSB-50K-3535A 2 x MBE1920-T4VVSB-50K-3535A 2 x MBE1920-T4MB-50K-3535A |
System Power | 10.56KW |
Eh Ave Infield | >300 lux |
Emin/Emax | >0.62 |
Eh Ave Outfield | >200 lux |
Emin/Emax | >0.32 |
GR Max | 38 |
ULR | 1% |